Lutron RA2 Select Wireless Occupancy Sensor LRF4-OCR2B-P-WH
Lutron Singapore Radio Powr Savr Wireless Occupancy/Vacancy Ceiling Sensor Lutron Radio Powr Savr occupancy / vacancy sensors are wireless, battery-powered, passive infrared (PIR) sensors that automatically control lights via RF communication to...
Lutron Singapore Radio Powr Savr Wireless Occupancy/Vacancy Ceiling Sensor
Features of Lutron Singapore Wireless Occupancy Sensor
• Wireless occupancy sensor has 3 settings available: Auto-On/Auto-Off, Auto-On Low-Light/Auto-Off, and Manual-On/Auto-Off
• Auto-On Low-Light feature will turn lights on automatically only if there is less than approximately 10 Lux (1 fc) of ambient light
• Vacancy-only model available to meet California (U.S.A.) Title 24 requirements
• Uses Clear Connect technology
• Passive infrared motion detection with exclusive Lutron XCT Technology for fine motion detection
• 360˚ coverage ranges from 324 ft2 (30.2 m2) to 676 ft2 (62.4 m2), depending on mounting height
• Simple and intuitive adjustments available for Timeout, Auto-On, and Activity settings
• Supports advanced occupancy features, such as dependent occupancy groups and customizable occupied/unoccupied presets in some systems
• Multiple sensors can be added for extended coverage. Refer to product specification submittal of receiving device to determine system limits
• Lens illuminates during test mode to verify ideal locations
• Multiple ceiling-mount methods available for different ceiling materials
• Front accessible test buttons make programming easy
• 10-year battery life design
• RoHS compliant
Specifications of Lutron Singapore Wireless Occupancy Sensor
Regulatory
• Lutron Quality Systems Registered to ISO 9001:2008
Power/Performance
• Operating voltage: 3 V-
• Operating current: 14 μA nominal
• Requires one CR 123 lithium battery
• 10-year battery life
• Non-volatile memory (saved changes are stored during power loss)
Environment
• Temperature: 32 ˚F to 104 ˚F (0 ˚C to 40 ˚C)
• For indoor use only
• Relative humidity: less than 90% non-condensing
Sensor Coverage Test
• Front accessible test button
• Lens illuminates orange in response to motion during test mode and is visible from 60 ft (18 m)
Wireless Communication Test
• Front accessible test button
• Turn associated loads on and off
Timeout Options
• 1 minute*
• 5 minutes
• 15 minutes (default setting)
• 30 minutes